Protection type: Fold back current limiting, recovers automatically after fault condition is removed.
Over Voltage
115%¡«135%
Protection type: Hiccup mode, recovers automatically after fault condition is removed
ENVIRONMENT
Working Temp., Humidity
-10¡æ¡«+50¡æ£»20%¡«90 %RH
Storage Temp., Humidity
-20¡æ¡«+85¡æ£»10%¡«95 %RH
Vibration
10¡«500Hz£¬2G 10min./1cycle, period for 60min, each along X, Y, Z axes
SAFETY
Withstand Voltage
I/P-O/P:3KVAC I/P-O/P:1.5KVAC O/P-FG: 0.5KVAC
Isolation Resistance
I/P-O/P, I/P-FG, O/P-FG: 100M Ohms/500VDC
STANDARD
Safety Standard
Design refer to UL1950,TUV EN60950
EMC Standard
Design refer to EN55022£¬EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11;ENV50204
OTHERS
Weight
1.9Kg
Packing
10pcs/19.5kg/1.22CUFT
NOTE
1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25¡æ of ambient temperature.
2.
Ripple & noise are measured at 20MHz of bandwidth by using a 12¡åtwisted pair-wire terminated with a 0.1¦Ì & 47¦Ì
parallel capacitor.
3.
Tolerance: includes set up tolerance, line regulation and load regulation.
4.
The power supply is considered a component which will be installed into a final equipment. The final equipment must
be re-confirmed that it still meets EMC directives.
Tel:0086-21-63504377
Fax:0086-21-63504478
E-mail:mw@ming-well.com
Copyright@2006 mingwell electronic Co.,Ltd
Sales Add:No.Shitai Road,Huangpu,Shanghai Add:No.1 Fengpu West Road,Nanqiao,Fengxian,area Shanghai China »¦ICP±¸05038095ºÅ